Airtronic Basic controllers have been specially designed for the control of Rosenberg housed instruments and they represent optimum comfort and safety in operation, monitoring and service of the system. The most up-to-date DDC technology is used. Amongst the advantages of this technology, the option of customer specific adjustment should be emphasised for very many applications.

Complete operation is carried out remotely via a remote control display on which all fault reports and conditions of the service are shown in writing.

The Airtronic Basic series is manufactured in accordance with VDE (Association of German Electricians)

guidelines. It is available for control of fans with belt drive by standard motors and fans with direct drive by

controllable external rotor motors.

Freely programmable controller with microprocessor, which allows customers' special requirements to be met

Operator unit with 4-line LCD display for messages in writing, 20 characters each

Suitable for front installation or wall mounting

8 digital message inputs (fault messages)

Can be expanded (e.g. subsequent insertion of a cooling sequence or of heat recycling possible)

Operating voltage 24V AC, max 10 VA

Recyclable housing

  Airtronic Basic for air handling units Rosenberg  

Control functions for Airtronic Basic for air handling units Rosenberg

Control

Circulation pumps dependent on load and outside temperature

Control of inlet/outlet air dampers

Smooth start mixed air damper

Mixed air damper control manual/automatic

Preheat function of the hot water air heater

Timer switch program

4 switch times per day can be set: temperature and fan level

Monitoring functions for Airtronic Basic for air handling units Rosenberg

Fire/smoke message

Alarm memory in which the last 10 alarm messages may be queried

Air flow monitoring in the inlet and outlet air

Programmable frost monitoring

Overload of inlet and outlet air fan

Filter monitoring in the inlet and outlet air

Cascade control

Inlet air temperature control

Room/inlet air or outlet/inlet air cascade control

Minimal or maximum limiting of the inlet air temperature

PI controller with 3 sequences: heating, cooling, heat recycling

Heating sequence: hot water heat register

Cooling sequence: water air cooler or cooling machine

Heat recycling sequence: plate heat exchanger, glycol circulation or rotary heat exchanger

Set point control according to the outside temperature

Summer/winter compensation

Fan control

3-step speed control with direct drive (external rotor motor)

Single speed with belt drive

Operation

User-friendly operation with 4-line LCD display

LCD operator console as a remote display

Ventilation functions

Supported heating operation

Supported cooling operation

Night ventilation function

Through ventilation function

Rosenberg service package

Switch box

All control devices are manufactured in accordance with VDE (Association of German Electricians)

guidelines and in accordance with EMV (electromagnetic compatibility) guidelines 89/336 EWG and

low voltage guidelines 73/023 EWG, type of protection IP55, plastic cable sheath plate for simple

electrical installation, completely wired and checked.

DDC compact regulator

Wired and preset in accordance with block circuit diagram (pp.14 - 34), assembled. Sensors, control

Valves and other peripherals are supplied loose with them.

Manufacturing services

Taking down and installing the switch box Main electrical connection (feeding in)

Electrical installation of the externally located distributed devices (e.g. temperature sensors, servomotors)

Connection of the heat/cold register with insertion of the control valves enclosed loose into each closed

loop controlled system, as well as assembly of the servo-motors supplied with them

 

The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email to info@rosenberg.com.vn